XL7 Prime

XL7 Prime – 7″ Farb-Touchscreen

7” WVGA TFT All-in-One Controller with dual Ethernet & CAN and Integrated I/O.

  • 7” Full Colour TFT Touchscreen Display, 5 function keys and a system key
  • LAN 1 – 10/100/1000 (Auto-MDIX) Ethernet LAN port
  • LAN 2 – with USB Dongle
  • Dual CAN ports for Fieldbus flexibility
  • Logic Scan Rates – 0.013ms/k Logic
  • Real Time Clock (± 90 secs/month)
  • USB 2.0 (mini-B) is available for programming
  • USB 2.0 Host port (A) is available for exchanging files with USB FLASH drives
  • 3 Ports (1 RS-232 & 1 RS-485 ½ duplex on first Modular jack (MJ1/2), 1 RS-232 0r RS-485 on second Modular Jack(MJ3))
  • Operating Temperature range -10 to +60 °C
  • High Capacity MicroSD Slot (support for up to 32GB)
  • GPRS and 3G Modem Support
  • CAN Protocols – CsCAN, CANopen, DeviceNet and J1939
  • 6 Models available, 5 with varying I/O 1 model without I/O
Compare

Overview

The XL7 Prime All-in-One controller is designed around a high-resolution, wide aspect ratio colour touchscreen, built-in I/O, networking options, removable MicroSD Card and USB ports.  It’s programmable by Horner APG’s industry recognised Cscape software and can control a wide range of different processes and machines from small to medium applications.  The XL7 Prime comes fully equipped with dual 100Mbps Ethernet ports built into every model.  No additional Ethernet add-ons or accessories are needed.  The XL7 Prime Ethernet support includes an integrated Web Server, FTP Host, Email, Modbus/TCP Master/Slave, Programming and more.

The XL7 Prime includes two CAN ports.  XL7 Prime I/O expansion is not limited to its Built-in I/O.

Specifications

CONTROLLER
Ladder Logic Memory 2 MB
Logic Scan Rate 0.02 mS/K
Removable Memory microSD
Local Comment Storage Yes
Floating Point Support Yes
AutoTune PID Capable Yes
OPERATOR INTERFACE
Characters / Pixels 800×480 (WVGA)
Display Technology 7″ TFT Color
Character Height selectable fonts
Number of Pages 1023
Fields or Objects per Page 1023
Total Keys 6
Function Keys 5
OEM Faceplate Available Yes
I/O
Built-in I/O Points 22-44
SmartStix, SmartRail, SmartBlock I/O Support yes, CsCAN and Ethernet
Digital Inputs / Outputs, max 2048 / 2048
Analog Inputs / Outputs, max 512 / 512
General Purpose Registers (words) 50000
General Purpose Internal Coils (bits) 32768 (16384 retentive)
ETHERNET/INTERNET
Ethernet Support Standard, 2 Ports
Remote Access WebMI, HTTP or EnvisionRV
Remote File Access FTP or EnvisionFX
IIoT Support MQTT (Sparkplug)
SERIAL COMMUNICATIONS
Total Active Ports 3
RS-232 Ports / RS-485 Ports RS-232 & RS-485; RS-232 / RS-485
PLC / Drive Protocols Yes
RTU / Modbus Master / Slave Yes
Serial ASCII In / Out Yes
USB Ports (A and Mini-B) Yes
NETWORKING
Integrated CAN Networks 2
Supported CAN Networks CsCAN plus 1 of the following; CsCAN, CANopen Master/Slave, DeviceNet Master, SAE J1939
Maximum CAN Distance 500m per segment, 4 segments maximum
Programming over CAN CsCAN only
PHYSICAL SPECIFICATIONS
Height 5.66″ / 144 mm
Width 8.27″ / 211 mm
Depth 2.72″ / 70 mm
I/O Module Depth COM option adds 0.5″ / 13 mm depth
OPERATING SPECS & STANDARDS
Operating Temperature* -0 to 60°C *Note: -40°C Low Temp Option, Contact Factory
Humidity (non-condensing) 5 to 95%
Product Certifications CE, C’, UL Class 1 Div II
Environmental Rating NEMA & UL Type 1, 3R, 4, 4x, 12, 12k, 13, ABS

Downloads

XL7 Prime Sales Sheet Download
XL Prime Series Accordion Brochure Download
XL Prime Series Presentation Download
Technical Documentation (Requires Login/Registration)
XL7 Prime User Manual Download
XL7 Prime Model 0 Datasheet Download
XL7 Prime Model 2 Datasheet Download
XL7 Prime Model 3 Datasheet Download
XL7 Prime Model 4 Datasheet Download
XL7 Prime Model 5 Datasheet Download
XL7 Prime Model 6 Datasheet Download

On-Board I/O

Selection Table

Model DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP391C100
HEXP391C112 12 6 4 4
HEXP391C113 12 12 4 2 2
HEXP391C114 24 16 4 2 2
HEXP391C115 12 12 4 2 2 2
HEXP391C116 12 12 4 2 6 4

There are 4 high-speed inputs of the total DC Inputs. There are 2 high-speed outputs of the total DC outputs. Model 2, 3 & 4 feature 12-bit Analogue I/O. Model 5 features 14/16-bit Analogue I/O. High-speed Outputs can be used for PWM and Pulse Train Outputs, currently limited to <65 kHz. Model 6 features a 17-bit analogue I/O.

HIGH-SPEED INPUTS

Number of Counters 2
Maximum Frequency 500 kHz each
Accumulator Size 32-bits each
Modes Supported Totalizer, quadrature, pulse measurement, frequency measurement, set-point controlled outputs
HIGH-SPEED OUTPUTS
Modes Supported Stepper, PWM

Built-In Expansion I/O

 

 

XDAC 2 channel analog output I/O option kit

 

 

 

 

 

XDAC 4 channel analog output I/O option kit

 

 

add on interface

 

 

Add-on Interface Kits

Remote I/O

Remote I/O available for this product includes:

Ethernet Based I/O
CsCAN Based I/O
CANopen Based I/O
Modbus RTU Based I/O

Networking

Integrated CAN Networks 1
Supported CAN Networks CsCAN, CANopen, DeviceNet Master, SAE J1939
Integrated Ethernet Ports 1 plus 1 on USB dongle
Supported Ethernet Protocols TCP/IP, Modbus TCP, FTP, SRTP, EGD, ICMP, ASCII

NTP (Network Time Protocol) allowing synchronisation of internet based Horner controllers to a centralised web based time server

WebMI Published directly from the Horner Controller, WebMI allows plant data to be monitored and controlled from your computer, tablet or other mobile device

Certifications

CE Certified Link to Certifications Page
ROHS & WEEE Compliance statement – July 01,2018 Link to Certifications Page
UL Certification Link to Certifications Page