Horner Automation at SPS Italia 2022

We are excited to exhibit a range of controllers from our Micro OCS series & XL Series with the latest features available for you to see in action at: SPS Italia, in Parma, 24th – 26th of May.
Here, we are presenting some of our upcoming additions to the Horner product family, the XL Prime Series and OCS I/O.

OCS I/O: Highly Expandable & Flexible Remote I/O for OCS

Maybe You Only Need One More…

Sometimes you only need a little bit. Start with the CNX116 – which includes I/O right on the base. Meant as the perfect small amount of complementary I/O, the CNX116 gives you (2) Flexible Inputs (Digital or 12-bit Analog), (2) Digital Outputs, (1) 16-bit Universal Analog Input and (1) 12-bit Analog Output right onboard. Two inputs that can be used for either digital or analog signals, giving it up to 3 analog inputs without even needing another module.

…Or Maybe You Need A Lot

With expandability up to 7 modules per base and 16 bases per network, OCSI/O can handle almost any amount of I/O needs. It even includes a CsCAN In and CsCAN Out port to allow you to easily daisy-chain multiple bases without requiring a lot of custom wiring.

and Configuration Is a Breeze

Whether it’s a little or a lot, OCS-I/O configuration is meant to be simple and effortless. It’s configured using Cscape software, so when wired up, it can find the base and autopopulate all installed modules automatically. From there you may only need to tweak a couple of configurations for the base or modules to be ready to go. Cscape also calculates the I/O power usage for you automatically, so you’ll never overload an I/O base.

ADU100

Analog Inputs 4
Resolution 16-bit
Supported Input Types RTD/TC/0-20mA/0-10V
Thermocouple Types J/K/T/E/N/R/S
RTD Types PT100, PT1000
Max Error at 25ºC 0.2%
Operating Air Temp -40ºC to 60ºC

DAC107

Analog Inputs 4
Resolution 12-bit
Output Ranges 0-20mA/4-20mA/ +/-10V
Minimum 10V Load 500Ω
Maxmum Current Load 500Ω
Max Error at 25ºC 0.2%
Operating Air Temp -40ºC to 60ºC

DIM620

AC Inputs 8
Commons per Module 1
Input Voltage Range 90 to 240VAC
Absolute Max Voltage 260 VAC
OFF to ON Response <20ms
ON to OFF Response <20ms
Operating Air Temp -40ºC to 60ºC

DIQ512

Digital Inputs 4
Input Voltage Range 12 to 24 VDC
Commons per Module 4
Relay Outputs 4
Max Output Voltage 120VAC
Max Output Current 3A each
Operating Air Temp -40ºC to 60ºC

DIQ616

DC Inputs 8
Input Voltage Range 12 to 24 VDC
Input Commons 1
DC Outputs 8
Absolute Max Voltage 32DC
Output Commons 1
Operating Air Temp -40ºC to 60ºC

DIQM502

Relay Outputs 4
Max Current per Relay 8A AC / 5A DC
Max Total Current 16A
Max Output Voltage 240VAC
Expected Life 100K @ Rated Load
Operating Air Temp -40ºC to 60ºC

CNX116

Max Number of Modules  7 per base
Flexible Inputs 2 (Digital or Analog)
Input Voltage Range 5V, 12V or 24V
Analog Input Types 0-20mA/4-20mA/0-10V
DC Outputs 2 (2A)
Output Voltage Range 10 to 30 VDC
Operating Air Temp -40ºC to 60ºC
Universal Analog In 1
Input Resolution 16-bit
Supported Input Types RTD/TC/0-20mA/0-10V
Max Error at 25ºC 0.2%
Analog Outputs 1
Output Resolution 12-bit
Output Ranges 0-20mA/4-20mA/0-10V

CNX116 Base

Flexible Inputs Digital or Analog DC Outputs Universal Analog Inputs Analog Outputs
2* 2 1 1

*I1 and I2 can be configured as either digital or analog inputs

Part Numbers

OCS-I/0 Ac Inputs DC Inputs Relay Outputs DC Outputs Universal Analog Inputs Analog Outputs
HE959ADU100 0 0 0 0 4 0
HE959DAC107 0 0 0 0 0 4
HE959DIM620 8 0 0 0 0 0
HE959DIQ512 0 4 4 0 0 0
HE959DIQ616 0 8 0 8 0 0
HE959DQM502 0 0 4 0 0 0

Please note: All above information about the OCS I/O is subject to change

XL Prime Series

For years, the Horner XL Series has enjoyed a reputation as the most highly functional All-in-one Controller available anywhere. These products are currently trusted with thousands of applications world-wide. The NEW XL Prime Series builds upon that proven reputation – offering new and existing users alike performance upgrades and a highly secure, modern memory
architecture. This is accomplished with a new Horner designed System on Module (SOM) – containing a faster CPU, onboard mass storage and 100% non-volatile memory. The only battery is a small coin cell – simply tasked with maintaining the clock.

If you are a new automation designer looking for an innovative, reliable control solution – the XL Prime Series offers a fully integrated product in hardware and software. If you are an existing XL Series user – your current application program will port straight through in less than 30 seconds. In either case you can’t go wrong!

Features

ALL-IN-ONE CONTROL – performs all machine functions in a unified hardware design; Logic Control, Operator Interface, I/O and Networking.

MODERN MEMORY ARCHITECTURE – based on a custom designed SOM (System on Module) utilizing a powerful ARM microprocessor and 100% nonvolatile
memory for reliability.

HIGH-PERFORMANCE LOGIC ENGINE – fast scan times solving user logic using Variable-based Advanced Ladder logic or the IEC 6-1131 language set.

ONLINE PROGRAMMING – make logic changes without stopping the controller.

HIGH-RESOLUTION COLOR TOUCHSCREEN – for detailed graphics and nearly instantaneous screen updates.

ADVANCED HIGH-SPEED COUNTER – four built-in counters supporting frequencies over 500 kHz.

INDUSTRIAL ETHERNET AND REMOTE CONTROL – Ethernet IP, Modbus TCP and BACnet IP; FTP file transfer, Email. WebMI* for web-based Remote Monitoring; Push data to the cloud with MQTT* Sparkplug. *WebMI/MQTT requires one-time license.

PLUG-AND-PLAY DATALOGGING – record machine and process variables to microSD or USB Flash Drive.

Further Details

CPU ARM
Logic Scan Rate 0.02ms/kB
Logic Program Size 2MB
Program Variables 50,000 words & 32,768 bits
I/O Variables 1,024 words & 4,096 bits
Logic Languages Horner Advanced Ladder
IEC 6-1131
Option 0 ARM
Option 2 12 DC in, 6 Relay Out, 4 – 12-bit Analog In
Option 3 12 DC in, 12 DC Out, 2 – 12-bit Analog In
Option 4 24 DC in, 16 DC Out, 2 – 12-bit Analog In
Option 5 12 DC in, 12 DC Out, 2 – 14/16-bit Analog In
(mA/V/Tc/mV/RTD), 2 – 12-bit Analog Out (mA/V)
Option 6 12 DC in, 12 DC Out, 6 – 14/17-bit Analog In
(mA/V/Tc/mV/RTD), 4 – 12-bit Analog Out (mA/V)
Remote I/O All Models Support SmartRail, SmartBlock,
SmartStix, SmartMod and OCSI/O

XL4 Prime

Part Number DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP251C100
HEXP251C112 12 6 4 4
HEXP251C113 12 12 4 2 2
HEXP251C114 24 16 4 2 2
HEXP251C115 12 12 4 2 2 2
HEXP251C116 12 12 4 2 6 4

XL6 Prime

Part Number DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP371C100
HEXP371C112 12 6 4 4
HEXP371C113 12 12 4 2 2
HEXP371C114 24 16 4 2 2
HEXP371C115 12 12 4 2 2 2
HEXP371C116 12 12 4 2 6 4

XLW Prime

Part Number DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP381C100
HEXP381C112 12 6 4 4
HEXP381C113 12 12 4 2 2
HEXP381C114 24 16 4 2 2
HEXP381C115 12 12 4 2 2 2
HEXP381C116 12 12 4 2 6 4

XL7 Prime*

DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP391C100
HEXP391C112 12 6 4 4
HEXP391C113 12 12 4 2 2
HEXP391C114 24 16 4 2 2
HEXP391C115 12 12 4 2 2 2
HEXP391C116 12 12 4 2 6 4

*XL7 Prime is Scheduled to Release September 2022

XL10 Prime*

XL10 Prime Equivalent Part Number DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXP505C100
HEXP505C112 12 6 4 4
HEXP505C113 12 12 4 2 2
HEXP505C114 24 16 4 2 2
HEXP505C115 12 12 4 2 2 2
HEXP505C116 12 12 4 2 6 4

*XL10 Prime is Scheduled to Release September 2022

XL15 Prime*

Model DC In DC Out Relays HS In HS Out mA/V In mA/V RTD/T mA/V Out
HEXT751C100
HEXT751C112 12 6 4 4
HEXT751C113 12 12 4 2 2
HEXT751C114 24 16 4 2 2
HEXT751C115 12 12 4 2 2 2
HEXT751C116 12 12 4 2 6 4

*XL7 Prime is Scheduled to Release early 2023

USB Ports USB A: Storage, WiFi (opt), Video
USB mini-B: Programming
Serial Ports 1 – RS-232 and 1 – RS-485
Addl RS232/RS485 on XL7, XL10, XL15
Serial Protocols Modbus Master/Slave, BACnet MSTP Slave SNP, DF1, ASCII, NMEA
Ethernet Ports 1 – XL4 Prime, XL6 Prime, XLW Prime
2 – XL7 Prime, XL10 Prime, XL15 Prime
Ethernet Protocols Modbus TCP Client & Server, BACnet IP Server, Ethernet IP I/O Device, Logix Tag Exchange, Ethernet Global Data, ASCII over Ethernet, WebMI, Email, FTP Server, NTP
CAN Ports 1 – XL4 Prime, XL6 Prime, XLW Prime
2 – XL7 Prime, XL10 Prime, XL15 Prime
CAN Protocols CsCAN, CANopen (Master & Slave)
J1939, DeviceNet Scanner
XL4 Prime mm

in

96 x 96 x 58
3.78 x 3.78 x 2.26
XL6 Prime mm

in

187 x 144x 47
7.34 x5.66 x 1.84
XLW Prime mm

in

187 x 144x 47
7.34 x5.66 x 1.84
XL7 Prime mm

in

211x 144 x 70
8.27 x5.66 x 2.72
XL10 Prime mm

in

304 x 231 x 62
11.94 x 9.08 x 2.43
XL15 Prime mm

in

371 x 320 x 104
14.57 x 12.6 x 4.08
Model Resolution Physical Keys
XL4 Prime 320 x 240 5
XL6 Prime 640 x 480 6
XLW Prime 800 x 480 0
XL7 Prime 800 x 480 6
XL10 Prime 640 x 480 8
XL15 Prime 1024 x 768 0

All memory is 100% non-volatile (non-battery dependent)

Removable Mass Storage microSD(>32GB)
USB (>32GB)
Onboard Mass Storage
(Program Storage)
EMMC (8GB)
High Speed RAM
(Variable Storage)
MRAM (128kB)
Video Playback USB Video, mp4
320 x 240
Audio Playback wav, mp3
XL7 Prime, XL10 Prime, XL15 Prime only
Primary Power Range 10-30VDC
Operating Temperature -10° to 60°C
Relative Humidity 5 to 95% (non-condensing)
UL Rating Class 1, Div 2; Groups A, B, C, D
UL Type Ratings 3R, 4, 4x, 12, 12k, 13
IP Rating IP65

Sales Sheet: Download   Presentation: Download